HONEYWELL VN8 SERIES 2-WAY/3-WAY FAN COIL VALVE (NON-SPRING RETURN TYPE)
Download Files
HONEYWELL_VN8_SERIES_INSTALLATION_MANUAL_(ENGLISH).pdf (2.73 MB)
HONEYWELL_VN8_SERIES_INSTALLATION_MANUAL_(CHINESE).pdf (2.58 MB)
HONEYWELL_DS_VN8_Oct_2019.pdf (279.77 KB)
HONEYWELL_VN8_SERIES_INSTALLATION_MANUAL_(ENGLISH).pdf (2.73 MB)
HONEYWELL_VN8_SERIES_INSTALLATION_MANUAL_(CHINESE).pdf (2.58 MB)
HONEYWELL_DS_VN8_Oct_2019.pdf (279.77 KB)
HONEYWELL VN8 SERIES 2-WAY/3-WAY FAN COIL VALVE (NON-SPRING RETURN TYPE)
VN = NON-SPRING RETURN TYPE
Model
VN = NON-SPRING RETURN TYPE
Model
HONEYWELL VN82C15PP (NON-SP. RET.) 2-WAY (1/2'' [DN15] PN20 BSPP IP42) (3-WIRE 220VAC 50/60HZ) FAN COIL VALVE
ACTUATOR
Operating power supply: 220VAC±10%, 110VAC±10%
24VAC±10%, 50/60Hz
Control mode: Electric 3-wire on-off
Non-spring return
Working temperature: 0~65°C
Working condition
relative humidity:
10%~90%RH
without condensate water
Power c onsumption: ≤6W (50Hz); ≤7.5W (60Hz)
Actuation time: Switch on≤15s, switch off≤15s
Protection rating: IP42
SCOPE OF APPLICATION
VALVE BODY
VN8 series electric control valves can be used at home and in commercial buildings to control the flow of hot or cold liquid. Each set includes electric actuator and valve body. The VN8 series offer a wide range of options in voltages and thread standards according to the usage of different regions and provides two-way and three-way valve bodies to meet most of the requirements in buildings control.
Applicable medium: Cold, hot water or 50% glycol solution
Applicable medium: Cold, hot water or 50% glycol solution
Fluid temperature range: 0~94°C
Working temperature: 0~65°C
Working condition relative humidity: 10%~90%RH
Nominal pressure: PN20
Leak-rate: 0.05%Kvs
Materials:
Valve body and ball — forging brass (HPb59-1)
Valve rod — stainless steel (0Cr18Ni9)
Valve seat — polytetrafluoroethylene (PTFE)
O-sealing ring — Ethylene-Propylene-Diene Monomer (EPDM)