HONEYWELL VBA216-F FLANGED TWO-WAY BALL VALVES
Download Files
HONEYWELL_CN7234A2008_34NM_+VA216-100F.pdf (4.37 MB)
Honeywell_VBA216-F_Motorised-Ball-Valve-2way-DN65-to-DN150.pdf (166.23 KB)
HONEYWELL_CN7234A2008_34NM_+VA216-100F.pdf (4.37 MB)
Honeywell_VBA216-F_Motorised-Ball-Valve-2way-DN65-to-DN150.pdf (166.23 KB)
HONEYWELL VBA216-F FLANGED TWO-WAY BALL VALVES
GENERAL
The flanged two-way ball valves are used for modulating control of hot / chilled water in heating, ventilating and air conditioning systems.
Honeywell CN7220A2007(20N.m) and CN7234A2007(34N.m) [CN7234A2008 34N.m 24VAC/DC] rotary actuators are recommendated to be used with VBA216F series.
Model (Full Set)
1) HONEYWELL CN7234A2008 34NM, 24VAC/VDC, MODULATING CONTROL+VBA216-100F 2-WAY DN100 (4'') PN16 KVS160 FLANGED BALL VALVES (TEMP:-5~120°C)
2) VBA216-065F/CN7220A2001 - 65mm Flanged Ball valve c/w 20Nm Mod Actuator
3) VBA216-080F/CN7220A2001 - 80mm Flanged Ball valve c/w 20Nm Mod Actuator
Model (Ball Valve)
HONEYWELL VBA216-100F 2-WAY DN100 (4'') PN16 KVS160 FLANGED BALL VALVES (TEMP:-5~120°C)
Model (Full Set)
1) HONEYWELL CN7234A2008 34NM, 24VAC/VDC, MODULATING CONTROL+VBA216-100F 2-WAY DN100 (4'') PN16 KVS160 FLANGED BALL VALVES (TEMP:-5~120°C)
2) VBA216-065F/CN7220A2001 - 65mm Flanged Ball valve c/w 20Nm Mod Actuator
3) VBA216-080F/CN7220A2001 - 80mm Flanged Ball valve c/w 20Nm Mod Actuator
FEATURES
Low seat leakage rate.
Accurate positioning to ensure state-of-the-art temperature control.
Easy mounting of directly coupled with electric actuator.
SPECIFICATIONS
Rated rotary angle 90° (adjustable)
Nominal pressure rating PN16
Flow characteristic Equal percentage (See Fig.1)
Rangeability See Table. 1
Leakage rate ≤0.01% of kVS
Valve body
End connections Flanged ( ISO7005-2)
Material Cast Iron (body)
Dimensions See Fig.2
Trim
Seat Reinforced PTFE
Ball Stainless Steel
Stem Stainless Steel
Medium Chilled and hot water, 50% glycol solution
Working temperature -5 ... 110 °C
* If you need temperature upto 150°C, please contact Honeywell.
Working temperature -5 ... 110 °C
* If you need temperature upto 150°C, please contact Honeywell.
SIZES AND FLOW CAPACITIES
Table 1. Sizes and flow capacities
Order Number Valve
Size Kvs Rangeability Close-off(KPa) Recommendatory
Actuator Torque
VBA216-065F DN65 63 452:1 700 20N.m
VBA216-080F DN80 100 367:1 700 20N.m
VBA216-100F DN100 160 345:1 700 34N.m
VBA216-125F DN125 250 200:1 700 34N.m
VBA216-150F DN150 350 187:1 400 34N.m