FLOWHOOD CFM-88-L Electronic Balometer Capture Hood
Download Files
Accuracy_Specifications_-_AirData_Multimeter.pdf (12.46 KB)
5_-_CFM-88L_(13-7-17).pdf (435.7 KB)
FlowHood_CFM-88-L-3_Calibration_Certificate_For_Arench_(30-12-15).pdf (1.59 MB)
FlowHood_CFM-88-L-3_Calibration_Certificate_For_Kej_Econmech_Sdn_Bhd_(3-9-15).pdf (1.78 MB)
AirData_Multimeter_@_ADM-850L.pdf (51.49 KB)
Eakonmech_CFM-88-L-3_Calibration_Certificate.pdf (717.56 KB)
FlowHood_Micromanometer_(No_Pricing).JPG (111.24 KB)
Accuracy_Specifications_-_AirData_Multimeter.pdf (12.46 KB)
5_-_CFM-88L_(13-7-17).pdf (435.7 KB)
FlowHood_CFM-88-L-3_Calibration_Certificate_For_Arench_(30-12-15).pdf (1.59 MB)
FlowHood_CFM-88-L-3_Calibration_Certificate_For_Kej_Econmech_Sdn_Bhd_(3-9-15).pdf (1.78 MB)
AirData_Multimeter_@_ADM-850L.pdf (51.49 KB)
Eakonmech_CFM-88-L-3_Calibration_Certificate.pdf (717.56 KB)
FlowHood_Micromanometer_(No_Pricing).JPG (111.24 KB)
FLOWHOOD CFM-88-L Electronic Balometer Capture Hood
Model
1) FlowHood CFM-88-L-1 Electronic (2' x 2' Top & Carrying Case)
Features
• DIRECT DIGITAL READOUT IN ENGLISH AND METRIC UNITS •
FOR AIRFLOW ONLY
Model
1) FlowHood CFM-88-L-1 Electronic (2' x 2' Top & Carrying Case)
2) FlowHood CFM-88-L-3 Electronic (2'x2/1'x4'/2'x4'' Hoods & Carrying Case)
Features
• DIRECT DIGITAL READOUT IN ENGLISH AND METRIC UNITS •
FOR AIRFLOW ONLY
• FAST, ACCURATE, EASY
• AUTO RANGE AND ZERO
• 25 TO 2500 CFM RANGE
• SUPPLY AND EXHAUST
• READINGS CORRECTED FOR AIR DENSITY
AIR FLOW:
Measured in cubic feet per minute (cfm) and litres per second (L/s) corrected for local air density. The measurement range is 25-2500 cfm supply and 25-1500 cfm exhaust. Accuracy is ±3% of reading ±7 cfm from 100 to 2000 cfm.
AIR DENSITY CORRECTION:
The air density correction range is 14-40 in Hg and 32ºF to 158ºF for correction of air flow measurements. The readings represent local density airflow corrected for the density effects of temperature and absolute pressure.
RESPONSE TIME:
Five seconds for air flows greater than 180 cfm, and up to eight seconds at less than 70 cfm.
POSITION SENSITIVITY:
Unaffected by position.
READOUT:
10 digit, 0.4", high contrast, liquid crystal display.
WEIGHT:
FlowHood unit with meter and 2'x2’ top, 9.7 lbs.
UNIT DIMENSIONS:
Height 40"; top 24"x24"; base 14"x14".
BATTERY LIFE:
3000 readings per charge, 500 recharge cycles.